20.2

Setting Example

The following is an example of the routing setting.
Ex.
Transient transmission from the request source (Network No.1) to the target (Network No.3) via Network No.2.
(1)
Network No.: 1
Station No.0
Request source
Network No.1
Station
(1)
Network No.
Request
1
source
The data is transferred to the relay station (2)
of the own network to go to the network No.3.
(2)
Network No.
Relay
(3)
2
station 1
The data is transferred to the relay station (4)
of the own network to go to the network No.3.
(4)
Relay
(5)
station 2
The data has been transferred to the network
No.3, and is to be transferred to (6).
(6)
Destination
station
20.3

Precautions

The precautions on the routing setting are as follows:
• For the multiple CPU system configuration, the same routing setting must be used for all CPUs.
(2)
(3)
Network No.: 1
Network No.: 2
Station No.3
Station No.0
Relay station 1
Network No.2
Request route
Relay station
Destination station
Network No.
Station No.
3
3
Relay station
Destination station
Network No.
Station No.
6
3
(4)
(5)
Network No.: 2
Network No.: 3
Station No.6
Station No.7
Relay station 2
Network No.3
Response route
(1)
(2)
(3)
The data has been transferred to the network
No.1, and is to be transferred to (1).
Relay station
(4)
Network No.
Station No.
2
(5)
The data is transferred to the relay station (3)
of the own network to go to the network No.1.
Relay station
Network No.
Station No.
3
The data is transferred to the relay station (5)
of the own network to go to the network No.1.
(6)
Network No.: 3
Station No.0
Destination station
Destination station
Network No.
0
1
Destination station
Network No.
7
1
20 ROUTING SETTING