Device/label access service processing setting

RnPCPU
RnPCPU
RnCPU RnENCPU
(Process)
(Redundant)
• When using a SIL2 Process CPU, refer to the following as well.
Page 605 FUNCTIONS
• When using a Safety CPU, refer to the following as well.
Page 535 FUNCTIONS
The user can specify the time or the execution timing of the device/label access service processing which is performed during
the END processing.
A request to the CPU module from a peripheral is processed by the device/label access service processing. A communication
response to a request from a peripheral varies depending on the scan time and the state of communication load. To create the
service processing environment suitable for the system, change the device/label access service processing setting as shown
below.
• Set a longer time for the device/label access service processing to improve a communication response to a peripheral.
• Set a shorter time for the device/label access service processing to reduce a scan time extension due to service
processing.
Note that communications to the CPU module from multiple peripherals may lower a communication response to each
peripheral. Thus, consider the performance of communication responses and the extension of scan time, and adjust the
service processing environment according to the system by methods such as setting a longer time for the device/label access
service processing or changing the parameter settings of peripherals so that the timeout time becomes longer.
Engineering tool
Ladder monitor
GOT
For functions to which the device/label access service processing setting can be applied, refer to the list
targeted for device/label access service processing setting. ( Page 937 Target list)
RnPSFCPU RnPSFCPU
RnSFCPU RnSFCPU
(Standard)
(Safety)
(Standard)
(Safety)
Device and label access service processing setting = 10% of scan time
Device and label access service processing time = 1ms
Device monitor
GOT
Control processing (at program execution)
Refresh processing
Program execution
Engineering tool
END processing
GOT A
The device/label access
service processing is
executed in the END
processing.
Device/label access
service processing
request
Engineering tool
GOT A
GOT B