Module Access Device - Mitsubishi Electric MELSEC iQ-R-R00CPU User Manual

Melsec iq-r series cpu module application user's manual
Table of Contents

Advertisement

21.6

Module Access Device

This device directly accesses from the CPU module to the buffer memory of the intelligent function module mounted on the
main base unit and extension base unit.
Specify this device with 'Un\Gn'. (Example: U5\G11)
Specified item
Un
Start I/O number of intelligent function modules
Gn
Buffer memory address
When reading/writing the buffer memory data using the module access device more than twice within a
program, the processing speed can be increased by conducting read/write operations at a single point of the
program using the FROM/TO instruction.
• When data is written using more than one module access device:
• When data is written at a single point of the program using the TO instruction:
(1) Store data to devices such as the data register (D).
(2) Write data to only one point in the program.
Value to be specified
Upper two digits when a start I/O number is described in three digits
(00H to FFH)
Example: 1F stands for X/Y1F0
0 to 268435455 (decimal)
MOVP
K0
MOVP
K10
MOVP
K5
MOVP
K100
MOVP
K0
MOVP
K10
MOVP
K5
MOVP
K100
T0
H0
K10
D0
U0\
G10
U0\
G11
U0\
G12
U0\
G13
D0
D1
(1)
D2
D3
(2)
K4
21.6 Module Access Device