Specifications

This section describes the specifications of the data logging function.
Functional specifications
The following table lists functional specifications.
Item
Number of data logging settings
Data storage location
Logging type
Data collection
Collection interval
Number of points for collection
AND conjunction
Data
Trigger logging
processing
File output
File name
File storage format
Data type
Data output format
Output file
Storage file
handling
switching
Auto logging
APPX
948
Appendix 13 How to Use CPU Module Logging Configuration Tool
Trigger condition
AND conjunction
Trigger logging range
Number of trigger establishments
(number of events that can be handled as
trigger)
Number of records
Unicode text file
Binary file
File switching timing
Maximum number of storage files
Specifications
*1
10
• SD memory card
• Data memory
• CPU built-in memory (function memory)
• Continuous logging
• Trigger logging
• Every scan operation
• Time specification
• Interrupt occurrence
• Condition specification (device/label specification, step No.
specification)
Maximum of 1280 (128 per setting)
AND conjunction of the device/label specification and step No.
specification is enabled.
• Condition specification (device/label change specification, step No.
specification)
• When trigger instruction executed
AND conjunction of the device/label change specification and step No.
specification is enabled.
Number of records specified before and after the trigger establishment
one
■SD memory card
Maximum of 1000000
■CPU built-in memory (function memory)
Maximum of 50000
Additional information plus file number
• Unicode text file
• Binary file
• Bit
• Word (signed)
• Double word (signed)
• Word (unsigned)
• Double word (unsigned)
• Single-precision real number
• Double-precision real number
• String
• Numeric string
• Time
• Decimal format
• Hexadecimal format
• Decimal fraction format
• Exponential format
• Word (signed)
• Double word (signed)
• Word (unsigned)
• Double word (unsigned)
• Single-precision real number
• Double-precision real number
• Number of records
• File size
1 to 65535
When inserting an SD memory card, which holds data logging setting, into
the CPU module, the data logging automatically starts based on the data
logging setting information on the SD memory card.
*2