SECURITY FUNCTION
RnPCPU
RnCPU RnENCPU
(Process)
• Only the SIL2 Process CPU and Safety CPU support the user authentication function.
This function serves to protect the user property stored in a personal computer and the user property inside modules in the
MELSEC iQ-R series system against threats such as theft, tampering, faulty operation, and unauthorized execution due to the
unauthorized access by an outsider. Use an appropriate security function according to the purpose as shown in the following
table:
User property
(1) Protection is provided against theft, tampering, and faulty operation resulting from unauthorized access by an outsider. (Protection for user property on a
personal computer)
(2) Protection is provided against theft, tampering, faulty operation, and unauthorized execution resulting from unauthorized access by an outsider. (Protection
for user property in CPU modules)
Data to be protected Purpose
Project
CPU module
17 SECURITY FUNCTION
318
RnPCPU
RnPSFCPU RnPSFCPU
RnSFCPU RnSFCPU
(Redundant)
(Standard)
(Safety)
(Standard)
(1)
Engineering tool
Personal computer
GOT
User property
MELSEC iQ-R series system
Prevents unauthorized access to programs (in units of
POU). (A password is used.)
Prevents unauthorized access to programs (in units of
program file). (A security key is used.)
Project data locked with a security key can only be
viewed with an engineering tool for which the same
security key has been registered.
Restricts access to projects on the personal computer
with a combination of user name and password. The
security level can be set individually for each user.
Prevents unauthorized execution of programs. (A
security key is used.)
Programs locked with a security key can only be
executed at modules for which the same security key has
been set.
Restricts access to projects in the CPU module with a
combination of user name and password. The security
level can be set individually for each user.
Prevents unauthorized read and write of files.
(A password is used.)
Blocks access from an invalid IP address by identifying
the IP address of an external device via Ethernet.
Limits access to just specific communication routes via
Ethernet. (A password is used.)
(Safety)
Personal computer (at another location)
Internet/
intranet
(2)
Function
Block password function
Security key authentication
function
User authentication function
Security key authentication
function
User authentication function
File password function
IP filter function
Remote password function
Reference
GX Works3 Operating Manual
• GX Works3 Operating Manual
• MELSEC iQ-R Ethernet User's
Manual (Application)
• SLMP Reference Manual
• MELSEC iQ-R Serial
Communication Module User's
Manual (Application)
MELSEC iQ-R Ethernet User's Manual
(Application)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents