PLC Inputs and Outputs Installation (optional)
Functions:
Type
Input
Output
Specifications
Inputs
•
Bipolar Input
•
Electrically isolated
•
0-30 VDC
•
Min. 10 VDC to assert
•
Sinks 10 mA at 24 VDC
PCM PLC Input Customer Output
NOTE: To connect a dry contact signal, route GND to
one terminal and connect 24 VDC signal through the dry
contact to the other terminal (see image below).
(customer supplied)
Customer
PCM
334784G
Function
ENABLE
Turns the controller on and off (rising edge enables, falling edge disables).
Integrated systems: Turn the heat on/off using the InvisiPac PLC input
(instead of this input). The pattern controller will be turned on by the InvisiPac
system once the InvisiPac goes inactive.
DISABLE
Disables the pattern controller (pull high to disable)
NOTE: DISABLE polarity can be changed with the invert disable input setting.
See General Setup (Screen 4), page 32.
PROGRAM
Bits select a program to run (1-15) i.e. 1010 selects program #10
SELECT
NOTE: 0000 disables PLC selection (local program selection ADM)
ALARM 1
Relay opens for active alarm(s) on Line 1
ALARM 2
Relay opens for active alarm(s) on Line 2
Vin (no polarity)
30 VDC Max
Dry Contact
"+"
(24 VDC)
"-"
(GND)
(Jumper Wire)
Description
Outputs
•
Dry contact output
•
0-24 VDC or 0-240 VAC
•
2A max
PCM PLC Output
Alarms indicated by output relays. See Troubleshoot-
ing Error Codes, page 45 for more details.
Code
Description
A40P
Over-current on accessory
power supply output
A4XP
Over-current on communication
cable output
A4_P
Over-current on valve output "_"
K4_P
Encoder "_" pulse rate exceeds
maximum limit
Wire Pattern Control Board
Customer Input
24 VDC, 240VAC, 2A
Max
To Customer Input