6-10 Terminal 53 Low Voltage; 6-13 Terminal 53 High Current; 6-22 Terminal 54 Low Current; 6-23 Terminal 54 High Current - Trane TR200 Instruction Manual

Hide thumbs Also See for TR200:
Table of Contents

Advertisement

6-10 Terminal 53 Low Voltage

Range:
0.07 V* [Application dependant]
6-11 Terminal 53 High Voltage
Range:
10.00 V* [Application dependant]
6-12 Terminal 53 Low Current
Range:
4.00
[Application dependant]
mA*

6-13 Terminal 53 High Current

Range:
20.00
[Application dependant]
mA*

6-22 Terminal 54 Low Current

Range:
4.00
[Application dependant]
mA*

6-23 Terminal 54 High Current

Range:
20.00
[Application dependant]
mA*
BAS-SVX19C-EN
How to program the Frequency Converter
Function:
Enter the low voltage value. This analog input scaling value should cor-
respond to the low reference/feedback value set in par. 6-14
Low Ref./Feedb.
Value.
Function:
Enter the high voltage value. This analog input scaling value should cor-
respond to the high reference/feedback value set in par. 6-15
53 High Ref./Feedb.
Value.
Function:
Enter the low current value. This reference signal should correspond to
the low reference/feedback value, set in par. 6-14
Feedb.
Value. The value must be set at >2 mA in order to activate the Live
Zero Time-out Function in par. 6-01
Function:
Enter the high current value corresponding to the high reference/feed-
back set in par. 6-15
Terminal 53 High Ref./Feedb.
Function:
Enter the low current value. This reference signal should correspond to
the low reference/feedback value, set in par. 6-24
Feedb.
Value. The value must be set at >2 mA in order to activate the Live
Zero Time-out Function in par. 6-01
Function:
Enter the high current value corresponding to the high reference/feed-
back value set in par. 6-25
Terminal 53 Low Ref./
Live Zero Timeout
Value.
Terminal 54 Low Ref./
Live Zero Timeout
Terminal 54 High Ref./Feedb.
Terminal 53
Terminal
Function.
Function.
Value.
6-37