How to program the Frequency Converter

6-14 Terminal 53 Low Ref./Feedb. Value

Range:
0.000*
[-999999.999 - 999999.999 ] Enter the analog input scaling value that corresponds to the low voltage/
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Applica-
[-999999.999 - 999999.999 ] Enter the analog input scaling value that corresponds to the high voltage/
tion de-
pend-
ent*

6-16 Terminal 53 Filter Time Constant

Range:
0.001 s* [0.001 - 10.000 s]
6-17 Terminal 53 Live Zero
Option:
[0]
Disabled
[1] *
Enabled

6-20 Terminal 54 Low Voltage

Range:
0.07 V* [Application dependant]

6-21 Terminal 54 High Voltage

Range:
10.00 V* [Application dependant]
6-22 Terminal 54 Low Current
Range:
4.00
[Application dependant]
mA*
6-38
Function:
low current set in par. 6-10
minal 53 Low
Current.
Function:
high current value set in par. 6-11
par. 6-13
Terminal 53 High
Function:
Enter the time constant. This is a first-order digital low pass filter time
constant for suppressing electrical noise in terminal 53. A high time con-
stant value improves dampening but also increases the time delay
through the filter.
This parameter cannot be adjusted while the motor is running.
Function:
This parameter makes it possible to disable the Live Zero monitoring.
E.g. to be used if the analog outputs are used as part of a de-central I/O
system (e.g. when not as part of any frequency converter related control
functions, but feeding a Building Management system with data).
Function:
Enter the low voltage value. This analog input scaling value should cor-
respond to the low reference/feedback value, set in par. 6-24
Low Ref./Feedb.
Value.
Function:
Enter the high voltage value. This analog input scaling value should cor-
respond to the high reference/feedback value set in par. 6-25
54 High Ref./Feedb.
Value.
Function:
Enter the low current value. This reference signal should correspond to
the low reference/feedback value, set in par. 6-24
Feedb.
Value. The value must be set at >2 mA in order to activate the Live
Zero Time-out Function in par. 6-01
Terminal 53 Low Voltage
Terminal 53 High Voltage
Current.
Terminal 54 Low Ref./
Live Zero Timeout
and par. 6-12
Ter-
and
Terminal 54
Terminal
Function.