How to program the Frequency Converter
24-** Application Functions 2
Par.
Parameter description
No. #
24-0* Fire Mode
24-00
Fire Mode Function
24-03
Fire Mode Min Reference
24-04
Fire Mode Max Reference
Fire Mode Preset Refer-
24-05
ence
Fire Mode Reference
24-06
Source
24-09
Fire Mode Alarm Handling
24-1* Drive Bypass
24-10
Drive Bypass Function
24-11
Drive Bypass Delay Time
6-92
Default value
4-set-up
[0] Disabled
2 set-ups
ExpressionLi-
mit
All set-ups
ExpressionLi-
mit
All set-ups
0.00 %
All set-ups
[0] No function
All set-ups
[1] Trip, Criti-
cal Alarms
2 set-ups
[0] Disabled
2 set-ups
0 s
2 set-ups
Change
Conver-
during op-
sion index
eration
TRUE
-
TRUE
-3
TRUE
-3
TRUE
-2
TRUE
-
FALSE
-
TRUE
-
TRUE
0
Type
Uint8
Int32
Int32
Int16
Uint8
Uint8
Uint8
Uint16
BAS-SVX19C-EN