20-94 Pid Integral Time; 22-22 Low Speed Detection; 22-23 No-Flow Function - Trane TR200 Instruction Manual

Hide thumbs Also See for TR200:
Table of Contents

Advertisement

If (Error x Gain) jumps with a value equal to what is set in par. 20-14
troller will try to change the output speed equal to what is set in par. 4-13
par. 4-14
Motor Speed High Limit [Hz]
The proportional band (error causing output to change from 0-100%) can be calculated by means of the formula:
(
)
1
× (
Max Reference
Proportional Gain
Always set the desired for par. 20-14
parameter group 20-9*.

20-94 PID Integral Time

Range:
20.00 s* [0.01 - 10000.00 s]

22-22 Low Speed Detection

Option:
[0] *
Disabled
[1]
Enabled

22-23 No-Flow Function

Common actions for Low Power Detection and Low Speed Detection (Individual selections not possible).
Option:
[0] *
Off
[1]
Sleep Mode
[2]
Warning
[3]
Alarm
BAS-SVX19C-EN
How to program the Frequency Converter
but in practice of course limited by this setting.
)
Maximum Reference/Feedb.
Function:
Over time, the integrator accumulates a contribution to the output from
the PID controller as long as there is a deviation between the Reference/
Setpoint and feedback signals. The contribution is proportional to the
size of the deviation. This ensures that the deviation (error) approaches
zero.
Quick response on any deviation is obtained when the integral time is
set to a low value. Setting it too low, however, may cause the control to
become unstable.
The value set, is the time needed for the integrator to add the same con-
tribution as the proportional part for a certain deviation.
If the value is set to 10,000, the controller will act as a pure proportional
controller with a P-band based on the value set in par. 20-93
tional
Gain. When no deviation is present, the output from the propor-
tional controller will be 0.
Function:
Select Enabled for detecting when the motor operates with a speed as
set in par. 4-11
Motor Speed Low Limit [RPM]
Low Limit
[Hz].
Function:
The drive will enter Sleep Mode and stop when a No Flow condition is
detected. See parameter group 22-4* for programming options for Sleep
Mode.
The drive will continue to run, but activate a No-Flow Warning [W92]. A
drive digital output or a serial communication bus can communicate a
warning to other equipment.
The drive will stop running and activate a No-Flow Alarm [A 92]. A drive
digital output or a serial communication bus can communicate an alarm
to other equipment.
Maximum Reference/Feedb.
Motor Speed High Limit [RPM]
before setting the values for the PID controller in
or par. 4-12
the PID con-
/
PID Propor-
Motor Speed
6-53

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents