Tips And Tricks; Quick Transfer Of Parameter Settings When Using Keypad; Data Storage In Keypad; Data Transfer From Keypad To Frequency Converter - Trane TR200 Instruction Manual

Hide thumbs Also See for TR200:
Table of Contents

Advertisement

Tips and Tricks

For the majority of HVAC applications the Quick Menu, Quick Set-up and Function Set-up provides the
simplest and quickest access to all the typical parameters required
Whenever possible, performing an AMA, will ensure best shaft performance
Contrast of the display can be adjusted by pressing [Status] and [
[Status] and [
Under [Quick Menu] and [Changes Made] all parameters that have been changed from factory settings
are displayed
Press and hold [Main Menu] key for 3 seconds for access to any parameter
For service purposes it is recommended to copy all parameters to the keypad, see par. 0-50
for further information

Quick Transfer of Parameter Settings when using keypad

Once the set-up of a frequency converter is complete, it is recommended to store (backup) the parameter settings
in the keypad or on a PC via TDU Set-up Software Tool.
Stop the motor before performing any of these operations otherwise unexpected operation can occur. Disconnect all
electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the
power can not be inadvertently energized.
Failure to follow recommendations could result in death or serious injury..

Data storage in keypad:

1.
Go to par. 0-50
LCP Copy
2.
Press the [OK] key
3.
Select "All to keypad"
4.
Press the [OK] key
All parameter settings are now stored in the GLCP indicated by the progress bar. When 100% is reached, press
[OK].
The GLCP can now be connected to another frequency converter and the parameter settings copied to this
frequency converter.

Data transfer from keypad to Frequency converter:

1.
Go to par. 0-50
LCP Copy
2.
Press the [OK] key
3.
Select "All from keypad"
4.
Press the [OK] key
The parameter settings stored in the GLCP are now transferred to the frequency converter indicated by the
progress bar. When 100% is reached, press [OK].
BAS-SVX19C-EN