Initialization To Default Settings; Manual Initialization - Trane TR200 Instruction Manual

Hide thumbs Also See for TR200:
Table of Contents

Advertisement

How to Operate the Frequency Converter

Initialization to Default Settings

There are two ways to initialize the frequency converter to default: Recommended initialization and manual
initialization.
Please be aware that they have different impact according to the below description.
Recommended initialization (via par. 14-22
tion
Mode)
1.
Select par. 14-22
Operation Mode
2.
Press [OK]
3.
Select "Initialization"
4.
Press [OK]
5.
Remove power to unit and wait for display to turn
off.
6.
Reconnect power and the frequency converter is
reset. Note that first start-up takes a few more
seconds
7.
Press [Reset]
Parameters selected in par. 0-25

Manual initialization

When carrying out manual initialization, serial communication, RFI filter settings and fault log settings are reset.
Removes parameters selected in par. 0-25
1. Disconnect from mains and wait until the dis-
play turns off.
2a. Press [Status] - [Main Menu] - [OK] at the
same time while power up for Graphical LCP
(GLCP)
3. Release the keys after 5 s
4. The frequency converter is now programd ac-
cording to default settings
5-12
Opera-
My Personal
Menu, will stay present, with default factory setting.
My Personal
Menu.
Par. 14-22
Operation Mode
Par. 14-50
RFI Filter
Par. 8-30
Protocol
Par. 8-31
Address
Par. 8-32
Baud Rate
Par. 8-35
Minimum Response Delay
Par. 8-36
Max Response Delay
Par. 8-37
Maximum Inter-Char Delay
Par. 15-00
Operating Hours
Volt's
Par. 15-20
Historic Log: Event
toric Log: Time
Par. 15-30
Alarm Log: Error Code
par. 15-32
Alarm Log: Time
This parameter initializes all except:
Par. 15-00
Operating Hours
Par. 15-03
Power Up's
Par. 15-04
Over Temp's
Par. 15-05
Over Volt's
initializes all except:
to par. 15-05
Over
to par. 15-22
His-
to
BAS-SVX19C-EN