1.9 Ratings

1.9.1 Short Circuit and Overcurrent Trips

The frequency converter is protected against short circuits with current measurement in each of the 3 motor phases or in
the DC link. A short circuit between 2 output phases causes an overcurrent in the inverter. The inverter turns off the IGBTs
individually when the short-circuit current exceeds the permitted value (Alarm 16 Trip Lock).

1.9.2 DC Voltage Levels

H1–H5
Inrush circuit enabled
Inrush circuit disabled
202
Undervoltage
202
Undervoltage re-enable
202+15
Overvoltage
410
Overvoltage re-enable
410-15
IT Grid Turn on
410+25
Table 1.8 DC Voltage Levels
BAS-SVM04B-EN
TR150 and TR170 Service Manual
200–240 V AC
H6–H8
H1–H5
I2–I3–I4
184
314
184
314
184+16
314+30
412
800
412-16
800-30
412+25
800+35
02/2017 All rights reserved.
380–480 V AC
H6–H8
H6–H10
I6–I8
372
532
372
532
372+24
532+20
800
976
800-24
976-20
800+35
976+35
1
1
525–600 V AC
17