3 And 6 Cable Motor Connection - Trane TR200 Instruction Manual

Hide thumbs Also See for TR200:
Table of Contents

Advertisement

WARNING
In motors without phase insulation paper or other insulation reinforcement suitable for operation with voltage supply
(such as a frequency converter), fit a sine-wave filter on the output of the frequency converter. (Motors that comply
with IEC 60034-17 do not require a Sine-wave filter) failure to do so could result in equipment damage.
No.
96
U
U1
W2
U1
No.
99
PE
Table 4. 8: 3 and 6 cable motor connection.
BAS-SVX19C-EN
97
98
Motor voltage 0-100% of mains voltage.
V
W
3 cables out of motor
V1
W1
6 cables out of motor, Delta-connected
U2
V2
V1
W1
6 cables out of motor, Star-connected
U2, V2, W2 to be interconnected separately
(optional terminal block)
Earth connection
Electrical Installation
4-19