How to program the Frequency Converter

Efficient Parameter Set-up for TR200 Applications:

The parameters can easily be set up for the vast majority of the TR200 applications only by using the [Quick
Setup] option.
After pressing [Quick Menu], the different choices in the Quick Menu are listed. See also illustration 6.1 below
and tables Q3-1 to Q3-4 in the following

Example of using the Quick Setup option:

Assume you want to set the Ramp Down Time to 100 seconds:
1.
Select [Quick Setup]. The first par. 0-01
2.
Press [
] repeatedly until par. 3-42
3.
Press [OK]
4.
Use the [
] button to highlight the 3rd digit before the comma
5.
Change '0' to '1' by using the [
6.
Use the [
] button to highlight the digit '2'
7.
Change '2' to '0' with the [
8.
Press [OK]
The new ramp-down time is now set to 100 seconds.
It is recommended to do the set-up in the order listed.
A complete description of the function is found in the parameter sections of this manual.
Figure 6. 1: Quick Menu view.
The Quick Setup menu gives access to the 18 most important setup parameters of the frequency converter. After
programming the frequency converter will, in most cases, be ready for operation. The 18 Quick Setup parameters
are shown in the table below. A complete description of the function is given in the parameter description
sections of this manual.
6-2
Function Setups
Language
in Quick Setup appears
Ramp 1 Ramp Down Time
] button
] button
section.
appears with the default setting of 20 seconds
BAS-SVX19C-EN