20-01 Feedback 1 Conversion; 20-02 Feedback 1 Source Unit - Trane TR200 Instruction Manual

Hide thumbs Also See for TR200:
Table of Contents

Advertisement

How to program the Frequency Converter
[4]
Pulse input 33
[7]
Analog input X30/11
[8]
Analog input X30/12
[9]
Analog Input X42/1
[10]
Analog Input X42/3
[11]
Analog Input X42/5
[12]
Analog Input X49/1
[13]
Analog Input X49/3
[14]
Analog Input X49/5
[100]
Bus feedback 1
[101]
Bus feedback 2
[102]
Bus feedback 3
NOTE: If a feedback is not used, its source must be set to
mines how the three possible feedbacks will be used by the PID Controller.

20-01 Feedback 1 Conversion

Option:
[0] *
Linear
[1]
Square root
[2]
Pressure to temperature

20-02 Feedback 1 Source Unit

Option:
[0] *
[1]
%
[5]
PPM
[10]
1/min
[11]
RPM
[12]
Pulse/s
[20]
l/s
[21]
l/min
6-44
No Function
Function:
This parameter allows a conversion function to be applied to Feedback
1.
Linear
[0] has no effect on the feedback.
Square root
[1] is commonly used when a pressure sensor is used to
provide flow feedback
flow
pressure
( (
) ).
Pressure to temperature
vide temperature feedback using a pressure sensor. The temperature of
the refrigerant is calculated using the following formula:
Temperature
=
(
(
ln
Pe
where A1, A2 and A3 are refrigerant-specific constants. The refrigerant
must be selected in par. 20-30 Refrigerant. Par. 20-21
par. 20-23
Setpoint 3
allow the values of A1, A2 and A3 to be entered for
a refrigerant that is not listed in par. 20-30 Refrigerant.
Function:
This parameter determines the unit that is used for this Feedback Source,
prior to applying the feedback conversion of par. 20-01
version. This unit is not used by the PID Controller.
[0]. Par. 20-20
Feedback Function
[2] is used in compressor applications to pro-
A
2
A
3 ,
+ 1 ) −
1 )
A
deter-
Setpoint 1
through
Feedback 1 Con-
BAS-SVX19C-EN