4-10 Motor Speed Direction; 4-53 Warning Speed High; 4-56 Warning Feedback Low; 4-57 Warning Feedback High - Trane TR200 Instruction Manual

Hide thumbs Also See for TR200:
Table of Contents

Advertisement

How to program the Frequency Converter
[27]
Analog Input X49/3
[28]
Analog Input X49/5
[30]
Ext. Closed Loop 1
[31]
Ext. Closed Loop 2
[32]
Ext. Closed Loop 3

4-10 Motor Speed Direction

Option:
[0]
Clockwise
[2] *
Both directions
The setting in par. 4-10
Motor Speed Direction

4-53 Warning Speed High

Range:
Applica-
[Application dependant]
tion de-
pend-
ent*
Any changes in par. 4-13
Motor Speed High Limit [RPM]
same value as set in par. 4-13
If a different value is needed in par. 4-53
Speed High Limit [RPM]

4-56 Warning Feedback Low

Range:
-999999.
[Application dependant]
999
Proc-
essCtrlU-
nit*

4-57 Warning Feedback High

Range:
999999.
[Application dependant]
999
Proc-
essCtrlU-
nit*
4-64 Semi-Auto Bypass Set-up
Option:
[0] *
Off
6-30
Function:
Selects the motor speed direction required.
Use this parameter to prevent unwanted reversing.
Only operation in clockwise direction will be allowed.
Operation in both clockwise and anti-clockwise direction will be allowed.
has impact on the Flying Start in par. 1-73
Function:
Enter the n
HIGH
the display reads SPEED HIGH. The signal outputs can be programd to
produce a status signal on terminal 27 or 29 and on relay output 01 or
02. program the upper signal limit of the motor speed, n
normal working range of the frequency converter. Refer to the drawing
in this section.
Motor Speed High Limit
[RPM].
Warning Speed
Function:
Enter the lower feedback limit. When the feedback falls below this limit,
the display reads Feedb Low. The signal outputs can be programd to
produce a status signal on terminal 27 or 29 and on relay output 01 or
02.
Function:
Enter the upper feedback limit. When the feedback exceeds this limit, the
display reads Feedb High. The signal outputs can be programd to pro-
duce a status signal on terminal 27 or 29 and on relay output 01 or 02.
Function:
No function
value. When the motor speed exceeds this limit (n
will reset the value in par. 4-53
High, it must be set after programming of par. 4-13
Flying
Start.
),
HIGH
, within the
HIGH
Warning Speed High
to the
Motor
BAS-SVX19C-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents