Basic information about the drive system

12.10 Rules for wiring with DRIVE-CLiQ

Figure 12-16 Topology view in STARTER
NOTICE
The Control Unit and the Option Board are not monitored. A replacement of components is
accepted automatically and not displayed.
12.10
Rules for wiring with DRIVE-CLiQ
Rules apply for wiring components with DRIVE-CLiQ. A distinction is made between binding
DRIVE-CLiQ rules, which must be unconditionally observed and recommended rules,
whichshould then be maintained so that the topology, generated offline in STARTER, no
longer has to be changed.
The maximum number of DRIVE-CLiQ components and the possible wiring type depend on
the following factors:
● The binding DRIVE-CLiQ wiring rules
● The number and type of activated drives and functions on the Control Unit in question
● The computing power of the Control Unit in question
● The set processing and communication cycles
Below you will find the binding wiring rules and some other recommendations as well as a
few sample topologies for DRIVE-CLiQ wiring.
The components used in these examples can be removed, replaced with others or
supplemented. If components are replaced by another type or additional components are
added, then the SIZER tool should be used to check the topology.
If the actual topology does not match the topology created offline by STARTER, the offline
topology must be changed accordingly before it is downloaded.