Efficiency Optimization - Siemens Sinamics S120 Function Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

4.15

Efficiency optimization

Description
The following can be achieved when optimizing the efficiency using p1580:
● Lower motor losses in the partial load range
● Noise in the motor is minimized
Figure 4-22
It only makes sense to activate this function if the dynamic response requirements of the
speed controller are low (e.g., pump and fan applications).
For p1580 = 100%, the flux in the motor under no-load operating conditions is reduced to
half of the setpoint (reference flux) (p1570/2). As soon as load is connected to the drive, the
setpoint (reference) flux linearly increases with the load and at approx. r0077 =
r0331 × p1570 reaches the setpoint set in p1570.
In the field-weakening range, the final value is reduced by the actual degree of field
weakening. The smoothing time (p1582) should be set to approx. 100 to 200 ms. Flux
differentiation (see also p1401.1) is automatically deactivated internally following
magnetization.
Function diagrams (see SINAMICS S120/S150 List Manual)
● 6722 Field weakening characteristic, Id setpoint (ASM, p0300 = 1)
● 6723 Field weakening controller, flux controller for induction motor (p0300 = 1)
Overview of important parameters (see SINAMICS S120/S150 List Manual)
● r0077 CO: Current setpoints, torque-generating
● r0331 Motor magnetizing current/short-circuit current (actual)
● p1570 CO: Flux setpoint
● p1580 Efficiency is optimization
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Efficiency optimization
Vector control
4.15 Efficiency optimization
181

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents