Extended setpoint channel
2.5 Jog
Parameterization with STARTER
In the STARTER commissioning tool, the "Motorized potentiometer" parameter screen in the
project navigator under the relevant drive is activated by double-clicking Setpoint channel →
Motorized potentiometer .
2.5
Jog
Description
This function can be selected via digital inputs or via a field bus (e.g. PROFIBUS). This
means that the setpoint is specified via p1058[0...n] and p1059[0...n].
When a jog signal is present, the motor is accelerated to the jog setpoint with the
acceleration ramp of the ramp-function generator (referred to the maximum speed p1082;
see diagram "Function chart: jog 1 and jog 2"). After the jog signal has been deselected, the
motor is decelerated via the set ramp of the ramp-function generator.
CAUTION
The "Jog" function is not PROFIdrive-compliant!
Figure 2-2
54
Function chart: jog and OFF1
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Drive functions