Siemens Sinamics S120 Function Manual page 584

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Communication
10.1 Communication according to PROFIdrive
● PROFIdrive parameter channel with the following data sets:
Characteristics of the parameter channel
● One 16-bit address each for parameter number and subindex.
● Concurrent access by several additional PROFIBUS masters (master class 2) or
582
– PROFIBUS: Data block 47 (0x002F)
The DPV1 services are available for master class 1 and class 2.
– PROFINET: Data block 47 and 0xB02F al global access, data set 0xB02E as local
access
Note
Please refer to the following documentation for a detailed description of acyclic
communication:
Reference: PROFIdrive Profile V4.1, May 2006, Order No: 3.172
Addressing:
• PROFIBUS DP, addressing is carried out via the logical address or the diagnostics
address.
• PROFINET IO, addressing is only undertaken using a diagnostics address which is
assigned to a module as of socket 1. Parameters cannot be accessed via socket 0.
Figure 10-16 Reading and writing data
PROFINET IO supervisor (e.g. commissioning tool).
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2