Vector control
4.26 Asynchronous pulse frequency
4. If output reactors or filters are connected to a Motor Module in the chassis format, when
5. The motor data identification must be performed with current controller cycles of 250 µs
Overview of important parameters (see SINAMICS S120/S150 List Manual)
● p0115[0...6] Sampling times for internal control loops
● p1810 modulator configuration
● p1840[0...n] Actual value correction configuration
214
dimensioning the reactors, the maximum pulse frequency must be taken into account and
for sine-wave filters, the minimum pulse frequency.
or 500 µs with 2 kHz.
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Drive functions