Siemens Sinamics S120 Function Manual page 641

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

IRT
Two options are available with this RT class:
● IRT "high flexibility"
● IRT "high performance".
Software preconditions for configuring IRT:
● STEP 7 5.4 SP4 (HW Config)
Note
For further information about configuring the PROFINET interface for the I/O controller and
I/O device, please refer to the following document: SIMOTION SCOUT Communication
System Manual.
IRT "high flexibility"
The telegrams are sent cyclically in a deterministic cycle (Isochronous Real Time). The
telegrams are exchanged in a bandwidth reserved by the hardware. One IRT time interval
and one standard Ethernet time interval are created for each cycle.
Note
IRT "high flexibility" cannot be used for isochronous applications.
IRT "high performance"
In addition to the bandwidth reservation, the telegram traffic can be further optimized by
configuring the topology. This enhances the performance during data exchange and the
deterministic behavior. The IRT time interval can thus be further optimized or minimized with
respect to IRT "high flexibility".
In addition to the isochronous data transfer provided by IRT, even the application itself
(position control cycle, IPO cycle) can be isochronous in the devices. This is an essential
requirement for closed-loop axis control and synchronization via the bus. Isochronous data
transfer with cycle times well below one millisecond and with a deviation in the cycle start
(jitter) of less than a microsecond provide sufficient performance reserves for demanding
motion control applications.
The RT classes IRT "high flexibility" and IRT "high performance" can be selected as options
in the synchronization settings configuration area of HW Config. In the description below,
both these classes are simply referred to as "IRT".
In contrast to standard Ethernet and PROFINET IO with RT, the telegrams for PROFINET IO
with IRT are transmitted according to a schedule.
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
10.3 Communication via PROFINET IO
Communication
639

Hide quick links:

Advertisement

Table of Contents