12.3.2 Common area (Memory Area No. 0)

Address Name
0000
Axis setting
Positioning repeat count
0001
(CH0)
Positioning repeat count
0002
(CH1)
Positioning repeat count
0003
(CH2)
Positioning repeat count
0004
(CH3)
0005
Reserved for system
-0006
0007
Error code
0008
Reserved for system
-0029
12-10
Default Description
Stores used channels (axes) and usage methods.
Monitor using binary display.
bit no.
Settings
0
Not use CH0 (0) / Use CH0 (1)
1
Not use CH1 (0) / Use CH1 (1)
2
Not use CH2 (0) / Use CH2 (1)
3
Not use CH3 (0) / Use CH3 (1)
H0
4-7
Disable the setting
As interpolation axis,
8
Not use CH0/CH1 (0) / Use
CH0/CH1 (1)
As interpolation axis,
9
Not use CH2/CH3 (0) / Use
CH2/CH3
10-15
Disable the setting
Stores the repeat count in decimal when using the
K0
repeat control in the position control.
Set value
K0
0 or 1
K0
2-254
255 or
K0
more
-
-
Stores a generated positioning error code in Hex
format (hexadecimal) when using the pulse output
function (table setting mode).
H0
The higher 8 bits indicate channel number.
The lower 8 bits indicate error code.
-
-
●: Available, -: Not available
Operation
Not repeat an operation.
Repeat an operation for a
specified number of times.
Repeat an operation infinitely.
R
W
-
-
-
-
-