System Register Settings - Panasonic FP0H User Manual

Control unit positioning/pwm output/high-speed counter
Hide thumbs Also See for FP0H:
Table of Contents

Advertisement

High-speed Counter Function

10.2 System Register Settings

10.2.1 System Register Settings
Functions to be used are allocated in the system register settings dialog box. The following
procedure is explained on the condition that the FPWIN GR7 has already started.
PROCEDURE
1. Select "Option" > "System register settings" from the menu bar.
The "PLC Configuration" dialog box appears.
2. Select "Controller input setting (HSC/PLS)" from the left pane.
The menu for setting "System register no. 400 or 401" appears.
3. Change the settings for the channels used for the high-speed counter.
The following figure shows the case when 2-phase input (X0, X1) is allocated to
CH0.
4. Press the [OK] button.
The screen returns to the ladder edit screen. The settings will be downloaded to
the PLC together with programs and comments.
10-6