Dm-Configuration Errors - Omron CJ1W-CT021 Operation Manuals

For nj-series cpu unit. high-speed counter units.
Hide thumbs Also See for CJ1W-CT021:
Table of Contents

Advertisement

Variable names
*_RdNxtErr
5-2-1

DM-configuration errors

An allocated DM area setting error is detected during the initialization processing when the Controller is
reset or the Unit is restarted.
When an allocated DM area setting error is detected, the error information is stored into memory and
the High-speed Counter Unit stops operation.
You can read the error information with the Read Next Error variable.
For the allocated DM area offset, refer to A-1-2 Differences in Access Methods from a User Program.
m in the table indicates the first word allocated in DM. m = D20000 + (N × 100) (N: Unit number)
Error Code 1
Error Code 2
0300
Offset (BCD)
0310
Offset (BCD)
0311
Offset (BCD)
0320
Counter
No.
0330
Counter
No.
0331
Counter
No.
CJ-series High-speed Counter Units Operation Manual for NJ-series CPU Unit(W492)
5 Error Processing, Maintenance and Inspection
Type
Name
BOOL
Read Next Error
Error
Out of Range
Illegal Value
Invalid Initial
Counter Value
Range
Invalid
No.
Range Limits
(BCD)
Range
Invalid
No.
Range Limit(s)/
(BCD)/
Comparison Value
CV No.
(BCD)
CV No.
Duplicate Target
(BCD)
Value
Function
When multiple errors occurred at the
same time, at the rising edge from 0 to 1,
the next error is read out from the error
list in this Unit.
Description
The DM-setting located at D20000 + (Nx100) + Offset is
Out of Range (N = Machine Number).
The BCD value of the allocated DM area (m+x (x: offset)
words) is invalid. (Any values other than 0 to 9 are
invalid.)
The Initial Counter Value located at D20000 + (Nx100) +
Offset is outside the counting range that is set for that
Counter (N = Machine Number).
Upper limit < Lower limit
Bits 00 to 11: Data No. (16#0001 to 16#0032)
Bits 12 to 15: Counter No. (16#1, 16#2)
If the Unit is in Range Mode: Lower and/or Upper Range
Limit is/are outside Counting Range. Counter No. indi-
cates the Counter number and Range No. indicates the
Range number.
If the Unit is in Comparison Mode: Comparison value is
outside Counting Range. Counter No. indicates the
Counter number and CV No. indicates the Comparison
Value number.
(The counting range of Circular and Linear Counters can
be specified, refer to 3-2-2 Circular Counter and 3-2-3
Linear Counter for more information).
Bits 00 to 11: Data numbers (16#0001 to 16#0032)
Bits 12 to 15: Counter numbers (16#1, 16#2)
For the Counter, with the Counter Number as reported in
Error Code 2, one or more Comparison Values are
equal. CV No. indicates the Comparison Value number.
Bits 00 to 11: Data numbers (16#0001 to 16#0032)
Bits 12 to 15: Counter numbers (16#1, 16#2)