Omron CJ1W-CT021 Operation Manuals page 175

For nj-series cpu unit. high-speed counter units.
Hide thumbs Also See for CJ1W-CT021:
Table of Contents

Advertisement

Item
Output State Control
Can select the method to control the output
states when the CPU operation mode is
changed or when an error occurs.
• Continue updating output states automati-
cally.
• Hold the output states.
• Bring the pre-defined output state.
External Output
External output drivers can be selected from
Driver Settings
the two types shown below.
• NPN
• PNP
Counter Reset Condi-
• Counter reset bit
tions
• External control input
• Z signal
Other Functions
• Programmable output pulse
• Pulse rate measurement functions
• Hysteresis
Noise Filter
• Encoder noise filter
• External control input noise filter
Counter Initial Values
• Counter initial values
IORD Instruction,
You can read or write the following data.
IOWR Instruction
• Allocated DM data
• Bandwidth comparison data and target value
match comparison data
• Captured Counter Value
• Pulse rate history log file data
• Counter value
• High-speed Counter Unit set and reset
• Error clear
Starting of External
You can use external output and internal output
Interrupt Task by Out-
unit output patterns to start CJ1-H/CJ1M CPU
put
Unit external interrupt tasks.
Starting of External
External control input can be used to start CJ1-
Interrupt Task by
H/CJ1M CPU Unit external interrupt tasks.
External Control Input
Error History Log
Up to 30
Functions
CJ-series High-speed Counter Units Operation Manual for NJ-series CPU Unit(W492)
Function in CJ series
10 kHz, 50 kHz, 500 kHz
10 kHz, 50 kHz
Function in NJ series
Same as on the left.
Same as on the left.
Same as on the left.
The pulse rate measurement function cannot
be used.
Same as on the left.
Same as at the left. However, because the NJ
Series has no power OFF interrupt task, opera-
tion cannot be restarted from the position at
which the power was interrupted.
The IORD/IOWR instruction cannot be used.
Therefore, you cannot read or write the data on
the left.
Cannot use.
Cannot use.
Same as on the left.
Appendices
A-3

Advertisement

Table of Contents
loading

Table of Contents