3 Operation and Configuration
3-3

Input Signal Types

Select the input type using the following device variables for CJ-series Unit (for setting). For every
Counter, you can select the Signal Type.
Name of device variable
for CJ-series Unit
*_Ch1_SigTypCfg
*_Ch2_SigTypCfg
3-3-1

Phase Differential

Phase Differential Signals are connected to the inputs A, B and Z of every Counter. The count direction
is determined by the phase angle between input A and input B. If signal A leads to B, the Counter incre-
ments. If signal B leads to A, the Counter decrements.
Phase A
Phase B
Multiplication x1
Multiplication x2
Multiplication x4
Multiplication x1
By default the Counter is configured for Multiplication by 1. If the Counter counts up (signal A leads
to signal B), pulses are taken into account by the Counter on the rising edges of signal A. If the
Counter counts down, pulses are taken into account on the falling edges of input A.
3-14
Type
UINT
Signal Type
Incremental encoder
Count up (CW)
1
2
3
1
2
3
4
5
6
1
2
3
4
5
6
7
8
9 10 11 12
CJ-series High-speed Counter Units Operation Manual for NJ-series CPU Unit(W492)
Name
This sets the input type.
0: Phase differential (multiplication 1)
1: Phase differential (multiplication 2)
2: Phase differential (multiplication 4)
4: Up & down pulse
8: Pulse & direction
Counter
Input A
A
Input B
B
Input Z
Z
(Reset i nput)
Count down (CCW)
2
1
5
4
3
2
11 10 9
8
7
6
5
4
Function
0
1
0
3
2
1
0