4 Exchanging Data with CPU
Name of device variable
for CJ-series Unit
*_Ch2_OutRstPatCfg
*_Ch2_HystrsCfg
*_Ch2_NumRngCmpCfg
*_Ch2_MemAreaCfg
*_Ch2_MemAdrCfg
*1 Set to "0" and turn OFF Hysteresis to use the Preset Function.
*2 Sets the beginning (k1) of the Range Data or Comparison Data.
4-22
Type
R/W
Name
DWORD R/W
Output Reset Pattern
UINT
R/W
Hysteresis
WORD
R/W
Number of
Ranges/Comparison
Values (BCD)
UINT
R/W
Memory Area
DWORD R/W
Memory Address
(BCD)
CJ-series High-speed Counter Units Operation Manual for NJ-series CPU Unit(W492)
Function
Sets the output (0 to 31) reset pattern.
Bits 00 to 31 correspond to output 0 to 31.
Each bit is reset for 1 and no change for 0.
Data range: 16#00000000 to 16#FFFFFFFF
Factory value: 0
Sets the hysteresis.
For 0, the hysteresis function is disabled.
Data range: 0 to 255
Unit: Pulse
Factory value: 0
Sets the number of ranges/comparison values as a
BCD.
Data range: 16#0000 to 0032
Factory value: 16#0000
Sets the area type for storing the range/comparison
data.
0: EM (factory value)
1: DM
Sets the start address (EM/DM) for storing the
range/comparison data as a BCD.
Data range: 16#00000000 to 00032760
Factory value: 16#0000