Name of device variable
for CJ-series Unit
*_OutCtlMdCfg
Additional Information
The Counter Output Patterns of Counters which are configured to use no (i.e. zero) Ranges, are
ignored in the AND-calculation of the Unit Output Pattern. Like this, Counters that you do not
want to use, do not influence the AND-calculation of the Unit Output Pattern. If both the Counters
are configured to use no Ranges, the output patterns for both outputs will be all OFF.
3-5-2

Comparison Mode

If the Unit is configured to control the Outputs in Comparison Mode, this Mode can be applied to Circu-
lar Counters or Linear Counters (refer to 3-2-2 Circular Counter and 3-2-3 Linear Counter for more
information).
CJ-series High-speed Counter Units Operation Manual for NJ-series CPU Unit(W492)
Type
Name
WORD
Output Control
Mode/AND/OR
Counter Output
Patterns
3 Operation and Configuration
Function
Bits 0 to 7: Output Control Mode
Sets the Output Control Mode.
16#00: Range Mode
16#01: Comparison Mode
Bits 8 to 15: Counter output pattern AND/OR
selection
For Range Mode, selects whether the
Counter output pattern is logically OR or
AND.
16#00: OR
16#01: AND