3.7.4

Commissioning with STARTER (example)

The table below describes the steps for commissioning a drive using the STARTER
commissioning tool.
What?
1.
Creating a new
project
2.
Automatic configu-
ration
3.
Configuring
the infeed
Note:
When the factory setting is p7826 = 1, the firmware is automatically updated to the status on the memory card when a
configured DRIVE-CLiQ component is first booted. This may take a few minutes and is indicated by the READY-LED on
the corresponding components flashing green/red and the LED on the Control Unit flashing orange (0.5 Hz). Once all up-
dates have been completed, the READY-LED on the Control Unit flashes orange at 2 Hz and the corresponding READY-
LED on the components flashes green/red at 2 Hz. For the firmware to be activated, a POWER ON must be carried out for
the components.
For infeed units connected to the drive unit, which during the automatic configuration do not communicate with the Control
Unit via DRIVE-CLiQ, you must manually configure and transfer them into the drive topology. These devices can only be
inserted in the offline mode.
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
3.7 Commissioning the vector control chassis format for the first time
How?
1. Call the "Project > New..." menu.
2. Enter a project name in the "New project" dialog.
3. Click "OK".
1. Call the "Project > Connect to selected target devices" menu.
As there is still no device available in the project, STARTER
offers the option of searching for accessible nodes.
2. Click "Yes".
3. Activate the drive unit accessed by clicking the checkbox.
4. Click "Accept".
The drive unit is transferred into the project window.
5. Call the "Project" > "Connect to selected target devices"
menu again.
You are now connected online with the drive unit.
6. Double-click "Automatic configuration". Click "Configure".
7. During automatic commissioning, the wizard will offer you the
option of selecting the drive object type. As default assign-
ment, select all of the "Vector" components.
8. Click "Create".
9. After the automatic configuration has been completed, you
have the option of going OFFLINE or remaining ONLINE. Se-
lect "Go OFFLINE".
1. Double-click "Infeeds" in the project navigator.
2. Double-click the infeed that has been created.
3. Click the yellow "Wizard..." button.
4. To check the automatic settings and to enter additional data,
such as equipment codes, etc. continue with step 3.2.