Commissioning
3.7 Commissioning the vector control chassis format for the first time
What?
9.
Save the parame-
ters on the device
10
The motor
starts to run
Important diagnostic parameters (see the SINAMICS S120/S150 List Manual)
• r0002
• r0046.0...31
154
How?
1. Select the drive unit in the project navigator.
2. Call the "Connect target device" shortcut menu.
3. Call the "Target device > Load into the target device" context
menu.
The "After loading, copy the RAM to ROM" option is active.
Click "Yes" to confirm the backup.
Or
4. Call the "Target device > Copy RAM to ROM" shortcut menu.
The drives can be started via the control panel in the STARTER
commissioning tool.
Line/DC-link identification will be carried out once the pulses
for the infeed have been enabled and line/DC-link identifica-
tion has been activated. The infeed then switches into the
"Operation" state.
When the pulses are enabled, a one-off motor data identifica-
tion run (if activated) is carried out.
When the pulses are enabled again, optimization with a rotat-
ing motor (if activated) is carried out.
Drive operating display
CO/BO:Missing enables
For further information, see Chapter "Diagnostics"
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
Comment
Position the cursor on the
drive unit (SINAMICS
S120) and right-click.
For more information about
the control panel, see Get-
ting Started.
During motor data identifi-
cation, a current flows
through the motor, which
means that it can align
itself by up to a quarter of a
revolution.
For more information about
line / DC-link / motor data
identification, see the
SINAMICS S120 Function
Manual Drive Functions.