STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
3.7 Commissioning the vector control chassis format for the first time
How?
Specify setpoint:
p1001 = 0 Fixed setpoint 1
p1002 = 40 Fixed setpoint 2
p1020 = r0722 Fixed speed setpoint selection
r1024 = p1070 Fixed setpoint active
1. Select the drive unit in the project navigator.
2. Call the "Connect target device" shortcut menu.
3. Call the "Target device" > "Load to target device" shortcut
menu.
To select a temperature sensor, you must set p0340 = 0.
1. Make the following settings:
The way in which the motor temperature is received
The temperature sensor type
For overtemperature, the response to alarm and fault (no
reduction of I
)
max
The alarm message when a sensor fails
The delay time to 0.100 s
The warning threshold to 120.0° C
The fault threshold to 155.0° C
Commissioning
Comment
A setpoint of 0 (0 signal) or
40 (1 signal) is defaulted
via digital input 7. This
setpoint is then applied to
the main setpoint p1070.
See function diagram
[3010]