Advertisement

5. Call the menu "Project > Accessible nodes" or click the symbol
search for available nodes in the Ethernet.
The SINAMICS drive unit is identified and displayed as bus participant Drive unit_1 with
IP address 169.254.11.22.
6. Select the bus node entry and select the shortcut menu "Edit Ethernet node...".
7. In the dialog "Edit Ethernet nodes", enter the device name for the Ethernet interface.
– Click "Assign name".
– If no entry is in the subnet mask, enter 255.255.0.0 in the subnet mask for the IP
– Click the "Assign IP configuration" button.
– Close the Information window "The parameters were transferred successfully".
– Click the "Close" button.
8. Click the "View/Refresh (F5)" button to display the IP address and the value
"NameOfStation" = "The assigned name" in the entry for the bus node.
Note
If these two pieces of information are not be displayed in the entry for the bus node, close
the "Accessible nodes" dialog and search for nodes that can be accessed again.
9. If the Ethernet interface is displayed as bus node, select the entry and click the "Accept"
button.
The SINAMICS drive is displayed as new drive object in the project tree. You can now
configure the new drive unit.
10.Click the "Connect to selected target devices" button and call the menu "Target system >
Load to target device", to load the project to the Control Unit memory card.
The IP address and device name are stored non-volatile on the memory card of the Control
Unit.
Parameterizing the interface in the expert list
1. Assign the "Name of Station" in parameter p8900
2. Assign the "IP Address of Station" in parameter p8901
(factory setting 169.254.11.22).
3. Assign the "Default Gateway of Station" in parameter p8902
(factory setting 0.0.0.0).
4. Assign the "Subnet Mask of Station" in parameter p8903
(factory setting 255.255.0.0).
5. Activate the configuration with p8905 = 1.
6. Activate and save the configuration with p8905 = 2.