Siemens Sinamics s120 Commissioning Manual page 310

With starter
Hide thumbs Also See for Sinamics s120:
Table of Contents

Advertisement

Diagnostics
4.1 Diagnostics via LEDs
Control Unit 320-2 PN in operation
Table 4- 7
Control Unit CU320-2 PN – Description of the LEDs after booting
LED
Color
RDY
(READY)
Green
Red
Red/
green
Orange
Green/
orange
or
red/
orange
PN
PROFIdrive
cyclic
operation
Green
310
State
Description, cause
OFF
The electronics power supply is missing or outside
the permissible tolerance range.
Continu-
The component is ready for operation and cyclic
ous light
DRIVE-CLiQ communication is taking place.
Flashing
Commissioning/reset
light
0.5 Hz
Flashing
Writing to the memory card
light
2 Hz
Flashing
General fault
light
2 Hz
Flashing
Control Unit is ready for operation.
light
However, there are no software licenses.
0.5 Hz
Flashing
Updating the firmware of the DRIVE-CLiQ compo-
light
nents.
0.5 Hz
Flashing
DRIVE-CLiQ component firmware update com-
light
plete. Wait for POWER ON for the components in
2 Hz
question.
Flashing
Component detection via LED is activated
light
(p0124[0]).
2 Hz
Note:
Both options depend on the LED status when
component recognition is activated via p0124[0] =
1.
Off
Cyclic communication has not (yet) taken place.
Note:
PROFIdrive is ready for communication when the
Control Unit is ready (see LED RDY).
Continu-
Cyclic communication is taking place.
ous light
Flashing
Full cyclic communication has not yet taken place.
light
Possible causes:
0.5 Hz
The controller is not transferring any setpoints.
During isochronous operation, no global con-
trol (GC) or a faulty global control (GC) is
transferred by the controller.
"Shared Device" is selected (p8929=2) and
only one controller connected.
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
Remedy
Check power supply
Check parameterization /
configuration
Obtain licenses
Turn POWER ON for the
components in question

Advertisement

Table of Contents
loading

Table of Contents