Commissioning
3.3 STARTER commissioning tool
3.3.4

Activating online operation: STARTER via Ethernet

The Control Unit can be commissioned with the PG/PC via the integrated Ethernet interface.
This interface is provided for commissioning purposes only and cannot be used to control the
drive in operation. Routing with a possibly inserted CBE20 expansion card is not possible.
Precondition
● STARTER as of version 4.1.5
● Control Unit CU320-2 DP as of version "C" or CU320-2 PN
STARTER via Ethernet (example)
Image 3-14
Install online operation via Ethernet
1. Install the Ethernet interface in the PG/PC according to the manufacturer's instructions.
2. Set the IP address of the Ethernet interface in Windows:
– Assign the PG/PC a free IP address (e.g. 169.254.11.1 ).
– In the delivery condition, the IP address of the internal Ethernet interface X127 of the
3. Set the access point of the STARTER commissioning tool.
4. Use the STARTER commissioning tool to specify a name for the Control Unit interface.
102
Connecting the PG/PC to the target device via Ethernet (example)
Control Unit is 169.254.11.22.
Note
Ethernet interface X127 is intended for commissioning and diagnostics.
Do not use this interface for other purposes and ensure that X127 is always
accessible (e.g. for service).
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5