Parameterizing And Testing The Temperature Sensors - Siemens Sinamics s120 Commissioning Manual

With starter
Hide thumbs Also See for Sinamics s120:
Table of Contents

Advertisement

Commissioning
3.13 Commissioning of SIMOTICS L-1FN3 linear motors
3.13.5

Parameterizing and testing the temperature sensors

SME12x Sensor Module External
The connection of the SME modules is described in the "System integration" chapter in the
"SIMOTICS L-1FN3 Linear Motors" Configuration Manual. Information on the SME12x
Sensor Module External can be found in the "SINAMICS S120 Equipment Manual for Control
Units and Additional System Components" in Chapter "Sensor Module External 120
(SME120)" and in Chapter "Sensor Module External 125 (SME125)".
The parameterization of the temperature sensors is explained in detail in Chapter
"Temperature sensors for SINAMICS components (Page 282)".
A parameterizing example of a linear motor with a PT1000 (or alternatively: KTY 84) and a
PTC sensor, connected to a SME12x Sensor Module External is provided below.
Use the expert list to parameterize the drive.
Table 3- 12
Parameter
p0600
p0601
p0604
p0605
p0606
200
Parameterization in the drive:
Input
Motor temperature sensor for monitoring
1: Temperature sensor via encoder 1
Motor temperature sensor, sensor type
10: Evaluation via several temperature channels SME12x
Motor temperature alarm threshold
Sets the alarm threshold for monitoring the motor temperature.
For motors from the motor list (p0301), this parameter is automatically pre-assigned
(120° C).
Motor temperature fault threshold
Sets the fault threshold for monitoring the motor temperature.
For motors from the motor list (p0301), this parameter is automatically pre-assigned
(155° C).
Motor temperature timer
0...2 s
Setting the timer for the alarm threshold for the motor temperature monitoring, if
alarm with timer was selected in the parameters p4600...4603.
This timer is started if the temperature alarm threshold (p0604) is exceeded.
If the timer has expired, and in the meantime the temperature alarm threshold has
not been undershot, then fault F07011 is output.
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5

Advertisement

Table of Contents
loading

Table of Contents