Commissioning
3.4 Creating a project in the STARTER commissioning tool
Add a single drive
1. Double-click in the project tree on "Insert single drive unit".
The following settings are pre-assigned:
– Device type: CU320-2 DP
– Device version: 4.5 or higher
– Address type: PROFIBUS/USS/PPI
– Bus address: 7
2. If necessary, correct the settings, and confirm with "OK".
Note
Bus address
The PROFIBUS address of the Control Unit must be set for initial commissioning.
Using the rotary coding switches on the Control Unit, the address can be set to a value
between 1 and 126 and read via p0918. If the coding switches are at "0" (factory setting),
the value can be alternatively set between 1 and 126 using p0918.
Configure the drive unit
Once you have created the project, you have to configure the drive unit. Some examples are
provided in the following Chapters.
116
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5