Table 3-7 Notes On The Feedback Bits - Siemens SIMATIC ET 200S Operating Instructions Manual

Technological functions
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Control bits
Notes
SET_DO2
Control bit DO2
Switches the DO2 digital output on and off when CTRL_DO2 is set.
SW_GATE
SW gate control bit
The SW gate is opened/closed via the control interface with the SW_GATE bit.
Notes on the Feedback Bits
Table 3-7
Notes on the Feedback Bits
Feedback bits
Notes
ERR_24V
Short circuit of the encoder supply
The error bit must be acknowledged with the EXTF_ACK control bit (see figure below).
Diagnostic message, if assigned.
ERR_DO1
Short circuit/wire break/overtemperature due to overload at output DO1
The error bit must be acknowledged with the EXTF_ACK control bit (see figure below).
Diagnostic message, if assigned.
ERR_DO2
Short circuit/wire break/overtemperature at output DO2
The error bit must be acknowledged with the EXTF_ACK control bit (see figure below).
Diagnostic message, if assigned.
ERR_ENCODER
Short circuit / wire break of 5 V encoder signal
The error bit must be acknowledged with the EXTF_ACK control bit (see figure below).
Diagnostic message, if assigned.
ERR_LOAD
Load function error (see figure below)
The LOAD_VAL, LOAD_PREPARE, CMP_VAL1, CMP_VAL2, and C_DOPARAM bits cannot be set
simultaneously during transfer. This results in setting the ERR_LOAD status bit, similar to loading an
incorrect value (which is not accepted).
ERR_PARA
Parameter assignment error ERR_PARA
RES_STS_A
Resetting of the status bits active (see figure below)
STS_C_DN
Down direction status
STS_C_UP
Up direction status
STS_CMP1
Comparator 1 status
The STS_CMP1 status bit indicates that the output is or was switched on. It must be acknowledged
with the RES_STS control bit. If the status bit is acknowledged when the output is still switched on,
the bit is set again immediately. This bit is also set if the SET_DO1 control bit is used when DO1 is
not enabled.
STS_CMP2
Comparator 2 status
The STS_CMP2 status bit indicates that the output is or was switched on. It must be acknowledged
with the RES_STS control bit. If the status bit is acknowledged when the output is still switched on,
the bit is set again immediately. This bit is also set if the SET_DO2 control bit is used when DO2 is
not enabled.
STS_DI
DI status
The status of the DI is indicated in all modes with the STS_DI bit in the feedback interface.
STS_DO1
DO1 status
The STS_DO1 status bit indicates the status of the DO1 digital output.
Technological Functions
Operating Instructions, 02/2007, A5E00124867-05