1Count5V/500kHz
3.6 Count Modes
3.6.11

Parameter Assignment for the Count Modes

Introduction
You can use either of the following to assign parameters for the 1Count5V/500kHz:
• A GSD file (http://www.ad.siemens.de/csi/gsd)
• STEP 7 V5.3 SP2 or later
Parameter List for Counting Modes
Table 3-9
Parameter List for Counting Modes
Parameter
Enable
Group diagnostics
Behavior in the event of the parent controller failing
Behavior at CPU/Master-STOP
Encoder parameters
Signal evaluation A, B
Diagnostics A and B
Diagnostics N
Direction input B
Output parameters
Function DO1
Function DO2
Substitute value DO1
Substitute value DO2
Diagnostics DO1
1
Diagnostics DO2
1
Hysteresis DO1, DO2
Pulse duration [2 ms] DO1, DO2
160
Value Range
Disable/enable
Turn off DO/
Continue working mode/
DO substitute a value/
DO keep last value
Rotary encoder single/double/quadruple
Off/on
Off/on
Normal/Inverted
Output/
Switch on at count ≥ comparison value/
Switch on at count ≤ comparison value/
Pulse on reaching the comparison value/
Switch at comparison values
Output/
Switch on at count ≥ comparison value/
Switch on at count ≤ comparison value/
Pulse on reaching the comparison value
0/1
0/1
Off/on
Off/on
0...255
0...255
Default
Disable
Turn off DO
Rotary encoder single
Off
Off
Normal
Output
Output
0
0
Off
Off
0
0
Technological Functions
Operating Instructions, 02/2007, A5E00124867-05