1Count24V/100kHz
2.8 Position Detection
2.8.7

Assigning Parameters for Position Feedback

Introduction
You can use either of the following to assign parameters for the 1Count24V/100kHz:
• A GSD file (http://www.ad.siemens.de/csi/gsd)
• STEP 7 V5.3 SP2 or later
Parameter List for Position Feedback
Table 2-29
Parameter List for Position Feedback
Parameter
Enable
Group diagnostics
Behavior in the event of the parent controller failing
Behavior at CPU/Master-STOP
Encoder parameters
Signal evaluation A, B
Encoder and input filter
- At count input (track A)
- At direction input (track B)
- At digital input DI
Sensor A, B, DI
Direction input B
Mode
Position feedback
Gate function
Input signal HW gate
Function DI
Synchronization
1
Only relevant if Function DI = Synchronization on positive edge
1
104
Value Range
Disable/enable
Turn off
Continue working mode
Pulse and direction/
Rotary encoder
single/double/quadruple
2.5 µs/25 µs
2.5 µs/25 µs
2.5 µs/25 µs
24V P switch, normal mode/
24V M switch
Normal/Inverted
Position detection
Cancel counting/
Interrupt counting
Normal/Inverted
Input/
HW gate/
Latch and retrigger on positive edge/
Synchronization on positive edge
Once-only/Periodic
Default
Disable
Turn off
Pulse and direction
2.5 µs
2.5 µs
2.5 µs
24V P switch, normal mode
Normal
Position detection
Cancel counting
Normal
Input
Once-only
Technological Functions