Feedback Data Record - Siemens SIMATIC ET 200S M151-3 PN Manual

Distributed i/o interface module
Table of Contents

Advertisement

Functions
3.3 Option handling
3.3.2

Feedback data record

Feedback data record
The feedback data record is mapped via a separate data record, 197.
The feedback data record only exists for configured option handling. It always refers to the
maximum quantity structure, which means 63 I/O slots. Partial reading is not possible.
Table 3- 5
Byte
0
1
2
3
4
5
:
66
Error Messages
The feedback data record will return the following error messages, if necessary:
Error code
0x80B1
0x80B5
0x80B8
26
Feedback data record
Element
Coding
Block length
67
Block ID
197
Version
1
0
Status, slot 1
1
Status, slot 2
2
:
:
Status, slot n
Maximum slot
Meaning
Invalid length
Option handling not configured
Parameter error
Meaning
Header
Bit 0 = 0: Reserve module, module removed or
invalid
Bit 0 = 1: Slot with correct module
Bit 1-7: Reserved
Interface module IM151-3 PN HIGH FEATURE (6ES7151-3BA23-0AB0)
Manual, 08/2010, A5E01584258-04

Advertisement

Table of Contents
loading

This manual is also suitable for:

6es7151-3ba23-0ab