Table 5-2 Parameter List For Heating A Liquid - Siemens SIMATIC ET 200S Operating Instructions Manual

Technological functions
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Parameters
The following parameters are required for channel 0 of the 2PULSE to heat a liquid in pulse-
width modulation mode.
Table 5-2
Parameter List for Heating a Liquid
Parameter
Group diagnostics
Diagnostics DO 0
Behavior at CPU/Master-STOP
Mode
PWM output format
Time base
Function DI 0
On-delay
Minimum/pulse duration
Period
The additional parameters of channel 0 of the 2PULSE have no effect on pulse-width
modulation mode.
The parameters for channel 1 are not relevant in this application example.
Technological Functions
Operating Instructions, 02/2007, A5E00124867-05
Set Value
Not enabled
On
Turn off DO 0
Pulse-width modulation
Per mill
1 ms
Input
0
500
30000
5.4 Application Examples
Meaning
The following errors trigger a diagnostic
message:
Short circuit of digital output
Short circuit of the encoder supply
Parameter assignment error
The 2PULSE detects the short circuit error on
the digital output DO 0.
The output value is specified in [‰] (0 to 1000)
All the preset times are specified at a resolution
of 1 ms.
The digital input is not required for this
application
The 24 V control signal is immediately output
with SW_ENABLE=1
Minimum pulse duration:
This is 500 ms in the selected time base; this
also applies to the minimum interpulse period
This is 30 s in the selected time base
2PULSE
297