Siemens SIMATIC ET 200S Operating Instructions Manual page 220

Technological functions
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

1SSI
4.1 Product Overview
• Fast mode can be selected; with rapid encoder value detection and compressed
• Maximum encoder sampling rate (e.g., for ultrasonic encoders) is taken into account in
• Sign of life in isochrone mode
• Parity check of encoder value can be performed
• Gray/dual converter
Supported Encoder Types
The following encoder types are supported:
• Absolute encoder (SSI) with 13 bits
• Absolute encoder (SSI) with 14 bits
• Absolute encoder (SSI) with 16 bits
• Absolute encoder (SSI) with 21 bits
• Absolute encoder (SSI) with 24 bits
• Absolute encoder (SSI) with 25 bits
Firmware update
1
To add functions and for troubleshooting, it is possible to load firmware updates to the
operating system memory of the 1SSI using STEP 7 HW Config.
Note
Notice!
When you start the firmware update, the old firmware is deleted. If the firmware update is
interrupted or canceled for any reason, the 1SSI will no longer function correctly as a result.
Re-launch the firmware update and wait until this has completed successfully. See also ET
200S Distributed I/O System Manual, section: Identification Data.
Identification Data
1
• Hardware release status
• Firmware release status
• Serial number
See also ET 200S Distributed I/O System Manual, section: Identification Data.
This function is only possible if the header module in use supports the necessary system
1
services.
220
functionality (cannot be used with the IM 151 with the order number
6ES7 151-1AA00-0AB0).
isochrone mode
Technological Functions
Operating Instructions, 02/2007, A5E00124867-05

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents