Error Codes; How To Construct Devicenet Network By Dvpdt02-H2; Application Example I - Delta DVPDT02-H2 Operation Manual

Devicenet slave communication module
Table of Contents

Advertisement

CR#
#103 ~ #202
#203 ~ #215
#216 ~ #250
#251
#252 ~ #254
#255
4.3

Error Codes

Code
00
E2
F0
F2
F3
F4
F5
F7
F8
F9
5

How to Construct DeviceNet Network by DVPDT02-H2

5.1

Application Example I

Target
Exchanging data between DVP-SV and DVP-EH2 MPU through DeviceNet.
Constructing DeviceNet network by using DVPDT02-H2
1. Constructing DeviceNet network
DVP-PLC Operation Manual
DeviceNet Slave Communication Module DVPDT02-H2
Attribute
Content
Input data
Get/Set
mappinig
Get
Error
Get
MPU status
Description
DVPDT02-H2 operates
normally.
I/O off-line
Dup_MAC_ID test has
failed.
Working power in low
voltage
Entering test mode
Bus-off
No network power detected
Internal error. GPIO
detection error.
Internal error.
Manufacturingerror.
Internal error. Configured
memory polling error.
High byte
Area for storing data from DeviceNet master to
DVPDT02-H2.
Set up by the system. DO NOT use it.
Reserved
Register for storing errors. See 19.4.3 for error codes.
Reserved
CR#255 = K0: MPU in STOP status
CR#255 = K1: MPU in RUN status
How to correct
--
1. Check if the network connection is normal.
2. Check if the master operates normally.
1. Make sure DVPDT02-H2 has a unique address.
2. Re-power DVPDT02-H2.
Check if the power of DVPDT02-H2 and MPU is normal.
Re-power DVPDT02-H2.
Re-power DVPDT02-H2
1. Check if the network cable works normally.
2. Check if the network power works normally.
Send your DVPDT02-H2 back to the manufacturer for
repair.
Send your DVPDT02-H2 back to the manufacturer for
repair.
Send your DVPDT02-H2 back to the manufacturer for
repair.
Low byte
9

Advertisement

Table of Contents
loading

Table of Contents