Siemens SIMATIC S5-115U User Manual page 585

Simatic s5 series cpu 941-7ub11 cpu 942-7ub11 cpu 943-7ub11 and cpu 943-7ub21 cpu 944-7ub11 and cpu 944-7ub21
Table of Contents

Advertisement

S5-115U Manual
Analog Ouptut Module 8 x ± 10 V; Floating
Technical Specifications
Number of outputs
Type of outputs
Output ranges
(rated value)
Load resistance
minimum 3.3 k
Load connection
Digital representation of
the output signal
Conversion time
Permissible overload
capability
approx.
Short circuit protection
Short circuit
current
approx.
Voltage between
the reference
potential of the load
(M
terminal)
ANA
and the housing
maximum 60 V AC/75 V DC
Linearity in the rated range
Operational error limits
(0 °C to 55 °C)
Cable length
- shielded
maximum 200 m (656 ft.)
Front connector
Isolation rating
Rated isolation voltage
(outputs to
)
- tested with
- max. capacitive load
including cable capacity
EWA 4NEB 811 6130-02b
8 voltage and current
Power supply
outputs
- rated value
floating (not between
- ripple V
the inputs)
- permissible range
(ripple included)
±10 V
Current consumption
- from 5 V (internal)
- from 24 V (external)
Load to M
-terminal
ANA
Power losses of
11 bits plus sign
the module
(1024 units= rated
value)
Weight
1 msec.
25 % (up to 1280
units)
yes
25 mA
±2,5 ‰ ±3 units
±6 ‰
46 pin
according to VDE 0160
500 V
<100 nF
Technical Specifications
24 V DC
3.6 V
PP
20 to 30 V
typically 0.25 A
typically 0.3 A
typically 8.5 W
approx. 0.4 kg (0.88 lb.)
(6ES5 470-7LB12)
15-55

Advertisement

Table of Contents
loading