Connecting Resistance Thermometers (e.g. PT 100) with 6ES5 460-7LA12
A constant-current generator supplies the series-connected resistance thermometers (max.
8 PT 100s) with a current of 2.5 mA over pins "S+" and "S -".
If you use the 498-1AA11 submodule, you must terminate the unused input channels with a short-
circuiting jumper (see Figure 10-6, range card 2; channels 5 and 6).
+
PT 100
¯ ¯ ¯
Channel 0
PT 100
Channel 1
Channel 2
PT 100
Channel 3
0 ... 500 mV
U
CM
U
Channel 7
PT 100
Figure 10-6. Connecting Resistance Thermometers (PT 100s) to a 460 Analog Input Module
If no PT 100 is connected to input channels 4 to 7, other voltages and currents can be measured on
these channels using range cards 498-1AA21, -1AA31, -1AA41, -1AA51, -1AA61 or -1AA71.
EWA 4NEB 811 6130-02b
M+
M –
Channel 4
0 ... 500 mV
CM
S –
S+
I
const
2.5 mA
Analog Value Processing
Range card 1
Range card
6ES5 498-
-1AA11
for 4 inputs
Range card 2
Range card
6ES5 498-
-1AA11
for 4 inputs
I –
I+
Reference bus
10-9