S5-115U Manual
Calling and Initializing
Parameter
Meaning
Analog value to be
XE
output
BG
Module address
KNKT
KN= channel
number
KT= channel type
Upper limit of the
OGR
output value
Lower limit of the
UGR
output value
Error when setting
FEH
the limit value
Analog value to be
BU
output exceeds
UGR or OGR
EWA 4NEB 811 6130-02b
-FB251-
Type
Data
Type
I
W
D
KF
KY =x,y
D
KY
x
y
0: unipolar representation
1: bipolar fixed-point number
D
KF
D
KF
"1" if UGR=OGR,
Q
BI
for illegal channel
or slot number,
or illegal channel type
At "1, "XE is outside the range
Q
BI
XE assumes the limit value
Analog Value Processing
Assignment
Input value
(fixed-point) in the
NAME
UGR to OGR range
XE
128 to 240
BG
KNKT
OGR
=0 to 7
=0;1
UGR
FEH
BU
- 32768 to +32767
- 32768 to +32767
(UGR;OGR).
STL
: JU FB 251
: RLG:AA
:
:
:
:
:
:
:
10-63