Connecting Loads to Current and Voltage Outputs
Figure 10-28 shows how to wire the analog output module.
QV (0)
S+ (0)
+
-
S - (0)
QI (0)
+
-
M
ANA
QV (0)
S+ (0)
+
-
S - (0)
M
ANA
Figure 10-28. Connecting Loads to Current and Voltage Outputs
Note
If voltage outputs are not used, or if only current outputs are connected, jumpers must
be inserted in the front connector for the unused voltage outputs. To do this, connect
QV (x) to S+(x) and S - (x) to M
Unused current outputs remain open.
EWA 4NEB 811 6130-02b
QV (1)
S+ (1)
+
-
S - (1)
QI (1)
+
-
6ES5 470-7LAxx
6ES5 470-7LCxx
QV (1)
S+ (1)
+
-
S - (1)
6ES5 470-7LBxx
ANA.
Analog Value Processing
QV (2)
S+ (2)
+
-
S - (2)
QI (2)
+
-
QV (2)
S+ (2)
+
-
S - (2)
10-57