Simatic s5 series cpu 941-7ub11 cpu 942-7ub11 cpu 943-7ub11 and cpu 943-7ub21 cpu 944-7ub11 and cpu 944-7ub21
Table of Contents

Advertisement

Integral Blocks
0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
10:
Cause of fault
(which fault has occurred?)
No fault
Start identifier (DB1) or end ident. (END) missing
Unterminated comment before END or semicolon
missing before END or END identifier missing
Block identifier syntax error or identifier
unknown
Parameter syntax error
Argument syntax error or overrange
Overrange in an argument
Illegal parameter combination
Not defined
Not defined
DB does not exist
Insufficient space in DB (e.g. in clock DB)
Error in specifying time
in the date
Error in time format
Error in hour format
Figure 11-6. Initialization Error Code and its Significance
Locating Parameter Errors in the ISTACK
If the PLC detects a parameter error in DB1 during restart, the PLC remains in the STOP state and
stores the asolute (error) address as well as the relative (error) address in the ISTACK. The STEP
address counter (SAC) in the ISTACK then points either
to the address that contains the wrong input or directly
in front of the address that contains the wrong input.
The addresses are byte addresses.
11-52
KH=
0 6 0 3
KH=
0 0 0 0
KH=
0 0 0 0
KH=
0 0 0 0
KH=
0 0 0 0
KH=
0 0 0 0
KH=
0 0 0 0
KH=
0 0 0 0
KH=
0 0 0 0
KH=
0 0 0 0
DWL
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Screen display with
parameter error codes
Fault Location
(in which parameter block has the
DWR
fault occurred?)
03
SL1: SINEC-L1
06
CLP:Clock parameters
09
TFB:Timer function block
10
PFB:Placement of FB (238/239)
11
SDP:System characteristics
99
ERT:Error return
F0
Fault cannot be attributed to a block
FF
Fault cannot be attributed to a block
S5-115U Manual